SAA certified cable
  • 0.6/1KV Australian standard low smoke halogen-free cable AS/NZS 5000.1 CU X-HF-110/HFS-110-TP

0.6/1KV Australian standard low smoke halogen-free cable AS/NZS 5000.1 CU X-HF-110/HFS-110-TP

This cable is a low smoke halogen-free cable that meets Australian standards. It is widely used in industrial and construction fields. It can also be used for trunk lines, branch lines and branch circuits. It can be unenclosed or enclosed in conduit sand in buildings and industrial plants that are not easily damaged by mechanical damage. There are also fire alarm systems, emergency lighting circuits and other occasions that require fire resistance.

EMAILEMAIL:momo.tao@aein-cable.com

Product introduction
  • 01 Product applicationThis cable is a low smoke halogen-free cable that meets Australian standards. It is widely used in industrial and construction fields. It can also be used for trunk lines, branch lines and branch circuits. It can be unenclosed or enclosed in conduits and in buildings and industrial plants that are not easily damaged by mechanical damage. There are also fire alarm systems, emergency lighting circuits and other occasions that require fire resistance.
  • 02 Product characteristics •SAA certification
    Flame retardant acc. to IEC 60332-1-2

    •Low smoke and halogen free in accordance with IEC60754

  • 03 Technical certification •Conform to RoHS standard
    •Conform to SAA Certificate•AS/NZS 5000.1:2005 Inc A1:2006
Product structure

Conductor material: bare copper wire

Conductor class: acc. to IEC 60228 cl. 5

Core insulation: X-HF-110 (low smoke zero halogen)

Core identification: Black core with white number, with or without GNYE

Stranding: stranded in layers

Outer sheath: HFS-110-TP (low smoke zero halogen)

Sheath color: black RAL 9005 Or gray RAL 7001 (optional)

Rated voltage: 0.6/1KV

Testing voltage: 2.5kV

Conductor resistance: acc. to ASNZS1125

Minimum bending radius fixed: 7.5x d

Minimum bending radius moved: 15x d

Temperature grade: -40°C/ +110°C

Burning behavior: self-extinguishing, acc. to IEC 60332-1 standard

Standard: AS/NZS 5000.1:2005 lnc A1:2006

Product identification: Aein bei ke    SHANGHAI AEIN  WIRE & CABLE  CO. .LTD   Model number   specification   Rated voltage 