Power, control and connecting cable for drive systems with frequency converter techno- logy, for fixed laying and casually movement without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use (black colour), but no laying underground.
• Conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
•
Conductor material: bare copper wire
Conductor class: acc. to IEC 60228 cl. 5
Core insulation: PE
Core identification: acc.to DIN VDE 0293-308 / GNYE Colored core
Stranding: stranded in layers
Shield: alu-lamin. polyester foil, metal side outside, cover. 100%
Sheath: PVC
Sheath color: blac kRAL9005; Transparent (optional)
Rated voltage: Uo/U: 0.6/1kV
Test voltage: 3.5 kV
Conductor resistance: acc.to IEC 60228 cl. 5
Insulation resistance: minimum 200MΩ x km
Minimum bending radius fixed:≤ 12mm Ø: 5 x d; ≤ 20mm Ø: 7.5 x d; > 20mm Ø: 10 x d
Minimum bending radius moved:≤ 12mm Ø: 10 x d; ≤ 20mm Ø: 15 x d; > 20mm Ø: 20 x d
Operat. temp. fixed min/max: -40 °C / +80 °C
Operat. temp. moved min/max: -15 °C / +80 °C
Temp. at conductor: + 90 °C Operating temperature; +250 °C Short-circuit temperature
Product identification: Aein bei ke SHANGHAI AEIN WIRE & CABLE CO.,LTD Model number specification voltage CE Meter scale