Power, control and connecting cable in electrical facilities, for fixed laying and casually movement without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms (also water-oil mixture). Outdoor use only with UV-protection, no laying underground.

EMAILEMAIL:info@aein-cable.com

Product introduction
  • 01 Product application Power, control and connecting cable in electrical facilities, for fixed laying and casually movement without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms (also water-oil mixture). Outdoor use only with UV-protection, no laying underground.
  • 02 Product characteristics increased resistance to oil by special PVC outer sheath, largely resistant to acids and bases acc. to EN 50363-4-1additional mechanical protection by inner sheath
  • 03 Technical certification

    conform to RoHS conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE

    We are pleased to produce special versions, other dimensions, core and jacket colours on request.

Product structure
Conductor material: Bare copper strand
Conductor class: Acc. to IEC 60228 cl. 5
Core insulation: PVC
Core identification: Acc. to DIN VDE 0293 black cores with white numerals; G = with GNYE
Stranding: Stranded in layers
Inner sheath material: PVC
Shield: Copper braid tinned, coverage approx. 85 %
Outer sheath: PVC
Sheath colour: Grey, RAL 7001
Rated voltage: Uo/U: 300/500 V
Testing voltage: 3 kV
Conductor resistance: Acc. to IEC 60228 cl. 5
Insulation resistance: Min. 20 MΩ x km
Current-carrying-capacity: Acc. to. DIN VDE, see technical Guidelines
Min. bending radius fixed: 6 x d
Min. bending radius moved: 12,5 x d
Operat. temp. fixed min/max: -40 °C / +70 °C
Operat. temp. moved min/max: -5 °C / +70 °C
Temp. at conductor: +70 °C in operation; +150 °C in case of short-circuit
Burning behavior: Self-extinguishing & flame-retardant acc.to IEC 60332-1
Standard: EN 50525-2-51 / VDE 0285-525-2-51