TKD CABLE
  • Alternative TKD H07Z-K Cable

Alternative TKD H07Z-K Cable

H05Z-K and H07Z-K as halogen-free and environmentally single core for internal wiring of devices as well as protected laying within and on shiners. Laying within pipes on-wall and in-wall permitted for signal facilities.

EMAILEMAIL:info@aein-cable.com

Product introduction
  • 01 Product application H05Z-K and H07Z-K as halogen-free and environmentally single core for internal wiring of devices as well as protected laying within and on shiners. Laying within pipes on-wall and in-wall permitted for signal facilities
  • 02 Product characteristicslargely resistant to acids, bases and specified types of oil
    halogen-free and flame-retardantno direct laying on pallets, in channels or trays (exceptional as potential compensation) all usual standard colours available
  • 03 Technical certification

    conform to RoHS conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE

     •We are pleased to produce special versions, other dimensions, core and jacket colours on request.

Product structure

Conductor material: LIHvz: copper strand tinned; H05Z-K, H07Z-K: bare copper strand.
Conductor class: Acc. to IEC 60228 class 5
Core insulation: Halogen-free special compound
Core identification: Different colours
Rated voltage: H05Z-K: 300/500 V; H07Z-K: 450/750 V peak voltage LiHvz: 500 V (0,14mm²), 900 V (0,25mm²)
Testing voltage: LiHvz: 1,2kV (0,14mm²) 2,5kV (0,25mm²) H05Z-K: 2kV; H07Z-K: 2,5kV
Conductor resistance: At +20 °C LiHvz acc. to VDE 0812; H05Z-K and H07Z-K acc. to IEC 60228
Current-carrying-capacity: Acc. to. DIN VDE, see Technical Guidelines
Min. bending radius fixed: 4 x d
Min. bending radius moved: 15 x d
Operat. temp. fixed min/max: -30 °C / +90 °C
Halogen free: Acc. to IEC 60754
Smoke density: Acc. to IEC 61034
Burning behavior: Self-extinguishing and flame-retardant acc. to IEC 60332-1-2
Standard: LiHvz similar to VDE0812; H05Z-K and H07Z-K acc. to EN 50525-3-41
Approvals: H05Z-K und H07Z-K: HAR