power, control and connecting cable in electrical facilities for lossless data and signal transmission, fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use only with UV-protection, no laying underground.
•conform to RoHS •conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
•We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: | Bare copper strand |
---|---|
Conductor class: | Acc. to IEC 60228 cl. 5 |
Core insulation: | PVC |
Core identification: | Coloured: up to 5 cores acc. to DIN VDE 0293-308; from 6 cores TKD colour code (see technical guideline); G: with GNYE |
Stranding: | Stranded in layers |
Inner sheath material: | PVC |
Shield3: | Copper braid tinned, coverage approx. 85 % |
Outer sheath: | PVC |
Sheath colour: | Transparent |
Rated voltage: | Uo/U: up to 16mm² 300/500V,from 25mm² 0,6/1kV |
Testing voltage: | 4 kV |
Conductor resistance: | Acc. to IEC 60228 cl. 5 |
Insulation resistance: | Min. 20 MΩ x km |
Current-carrying-capacity: | Acc. to DIN VDE, see technical Guidelines |
Min. bending radius fixed: | 6 x d |
Min. bending radius moved: | 15 x d |
Operat. temp. fixed min/max: | -40 °C / +80 °C |
Operat. temp. moved min/max: | -15 °C / +70 °C |
Temp. at conductor: | +70 °C in operation; +150 °C in case of short-circuit |
Burning behavior: | Self-extinguishing & flame-retardant acc.to IEC 60332-1 |