•conform to RoHS •conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
            
            
            
            
            
•We are pleased to produce special versions, other dimensions, core and jacket colours on request.
| Conductor material: | Bare copper strand | 
|---|---|
| Conductor class: | Acc. to IEC 60228 cl. 6 | 
| Core insulation: | PVC | 
| Core identification: | Acc. to DIN VDE 0293 black cores with white numerals; G = GNYE | 
| Stranding: | Cores stranded in layers | 
| Outer sheath: | PVC | 
| Sheath colour: | Black RAL 9005 | 
| Rated voltage: | IEC: 300/500 V; UL/CSA: 600V (TC, MTW, CIC), 1.000V (WTTC, AWM) | 
| Testing voltage: | 6 kV | 
| Conductor resistance: | At +20 °C acc. to IEC 60228 cl. 6 | 
| Insulation resistance: | At +20 °C ≥ 20 MΩ x km | 
| Current-carrying-capacity: | Acc. to DIN VDE | 
| Min. bending radius fixed: | 4 x d | 
| Min. bending radius moved: | 7,5 x d < 10m TL | 10 x d ≥ 10m TL | 
| Operat. temp. fixed min/max: | -40 °C / +90 °C | 
| Operat. temp. moved min/max: | -5 °C / +90 °C | 
| Burning behavior: | Flame-retardant acc. to IEC 60332-1, IEC 60332-3A, UL: Vertical-Tray Flame Test, CSA; FT4 | 
| Resistant to oil: | UL 1277 and UL 1063 (oil-resistant acc. to UL OIL RES I and water-resistant, UL wet approval 75 °C) | 
| Standard: | UL 1277, UL 1063 (MTW), NEC 336.10 (7) class1, Div. 2 acc. NEC Art. 336, 392, 501 | 
| Approvals: | UL/CSA - cULus & cURus 1.000V, 90°C (AWM, WTTC) and cULus & cURus 600V, 90°C (TC-ER, MTW, CIC) | 
| Acceleration: | Max. 10 m/s² |