exclusively for use in self-protective circuits, as impulse and data transmission cable, control and connecting cable in process controlled facilities in measurement and control technology for lossless data and signal transmission. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.
•conform to RoHS •conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
•We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Product structure
Conductor material: | Bare copper strand |
---|---|
Conductor class: | Acc. to IEC 60228 cl. 5 |
Core insulation: | PVC |
Core identification: | Acc. to DIN VDE 0293 black cores with white numerals but without GNYE |
Stranding: | Stranded in layers |
Shield3: | Copper braid tinned; coverage approx. 85% |
Outer sheath: | PVC |
Sheath colour: | Blue, RAL 5015 |
Rated voltage: | Uo/U: 300/500 V (see special features) |
Testing voltage: | 3 kV |
Conductor resistance: | Acc. to IEC 60228 cl. 5 |
Insulation resistance: | Min. 20 MΩ x km |
Current-carrying-capacity: | Acc. to DIN VDE, s. Techn. Guidelines |
Capacity: | Core/core ca. 120 nF/km; core/shield ca. 160 nF/km |
Min. bending radius fixed: | Up to 12 mm Ø 5 x d; > 12 mm Ø 7,5 x d |
Min. bending radius moved: | Up to 12 mm Ø 10 x d; up to 20 mm Ø 15 x d; > 20 mm Ø 20 x d |
Operat. temp. fixed min/max: | -30 °C / +80 °C |
Operat. temp. moved min/max: | -5 °C / +70 °C |
Burning behavior: | Self-extinguishing & flame-retardant acc.to IEC 60332-1 |
Standard: | Similar to DIN VDE 0812 |