Instrumentationcable for optimal, lossless transmission of analogous and digital signals in measurement and process control technology. Suitable for intrinsically safe systems zone 1 and zone 2 group II classified areas acc. IEC 60079-14. Suitable for dry and humid rooms as well as outdoor use and laying underground.
EMAIL:service@aein-cable.com、momo.tao@aein-cable.com
•conform to RoHS •conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
•We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Product structure
| Conductor material: | Bare copper strand |
|---|---|
| Conductor class: | 7-wired construction acc. to IEC 60228 cl. 2 |
| Core insulation: | XLPE (cross-linked polyethylene) |
| Core identification: | Pairs pairs: single-coloured with numerals: core A: black, core B: white; triple: single-coloured, core A: white, core B: red, core C: black, core A and C with numerals |
| Stranding: | Pairs stranded in layers |
| Inner sheath material: | PVC, black |
| Shield3: | Galvanized round or flat steel-wires (SWA) |
| Outer sheath: | PVC |
| Sheath colour: | Black or blue RAL 5015 for intrinsically safe systems |
| Rated voltage: | 300 V |
| Testing voltage: | Core/core (AC/DC): 1.5 / 2 kV (duration 1 minute) |
| Conductor resistance: | 0.5mm²: max.36.7 Ω/km; 0.75mm²: max.25.0 Ω/km; 1.3mm²: max.14.2 Ω/km |
| Insulation resistance: | Min. 5 GΩ x km |
| Current-carrying-capacity: | Acc. to DIN VDE, s. Techn. Guidelines |
| Capacity: | Max.115 nF/km |
| Inductivity: | Ca. 1 mH/km |
| Coupling: | Max. 500 pF/500 m |
| Min. bending radius fixed: | 10 x d |
| Operat. temp. fixed min/max: | -40°C / +70°C |
| Operat. temp. moved min/max: | -5°C / +50°C |
| Burning behavior: | Self-extinguishing and flame-retardant acc. to IEC 60332-1-2 and IEC 60332-3-24 (Cat. C) |
| Resistant to oil: | ICEA S-73-532 / NEMA WC 57-2004 § 6.9.3 |