EAC certified cable
  • FG16OH2M16, TUV German standard certification

FG16OH2M16, TUV German standard certification

Suitable for indoor and outdoor installation, also suitable for wet places and external installation; For mounting on surface-mounted or metal structures; It is allowed to be buried directly in the ground. When a certain level of protection is required against electromagnetic interference, it is usually used for the interconnection of machines or machine components.

EMAILEMAIL:momo.tao@aein-cable.com

Product introduction
  • 01 Product application

    Suitable for indoor and outdoor installation, also suitable for wet places and external installation; For mounting on surface-mounted or metal structures; It is allowed to be buried directly in the ground. When a certain level of protection is required against electromagnetic interference, it is usually used for the interconnection of machines or machine components.

  • 02 Product characteristics

    · Flame retardant in accordance with IEC 60332-1-2
    · Halogen-free according to IEC 60754-1:2011(total amount of halogen acid gas)
    · Corrosivity of combustion gas in accordance with IEC 60754-2:2011(acidity)
    · Low smoke density in accordance with IEC 61034-2:2005+A12013+A2:2020
    · Customization is acceptable for products with special structures, other sizes, cores and colors of sheathing.

  • 03 Technical certification

    · Comply with RoHS standards
    · Comply with Directive 2014/35/EU-Guideline (" Low Voltage Directive ")CE
    ·Comply with TUV certification

Product structure

Conductor material: bare copper wire

Conductor type: Compliant with IEC 60228 cl.5 cl.2 Optional

Insulation :G16 rigid ethylene-propylene rubber (HEPR) compound

Shielding: Copper wire braid shielding tinning wire is optional

Sheath :M16 type halogen-free thermoplastic compound

Core identification: two cores red and blue; Three core red yellow green; Four core red yellow green blue; Five core red yellow green blue yellow/green

Jacket color: Grey RAL7001

Stranding: stranding in layers

Rated voltage :0.6/1kV

Test voltage: 3.5kV

Conductor resistance: According to IEC 60228 cl.5 standard

Conductor rated temperature :90°C

Small bending radius fixed :7.5x d

Small bending radius movement :15x d

Fixed temperature: -40 °C /+90°C

Moving temperature :-25°C/+90°C

Flame retardant grade :IEC 60332-1-2, EN50265-2-1

Standard :IEC60502-1, DIN VDE 0295

Product identification: Aein bei ke SHANGHAI AEIN WIRE & CABLE CO.LTD Model Specification Voltage CE meter standard