Halogen-free and environmentally friendly data transmission, control and connection cables are used primarily for the transmission of analog and digital signals in process control facilities of measurement and control technologies, and for the lossless transmission of data and signals in fire-prone areas and facilities with high concentrations of personnel and property values. Suitable for fixed laying and flexible applications, no clear cable path, no tensile stress. Suitable for dry and wet indoor use.
Conductor material: bare copper wire
Conductor class: In accordance with IEC 60228 cl. 5standard
Insulation:HDPE,XLPE(Optional)
Identification of core wire: < 0,5 mm²:5Core and below the use of color separation, in line withn. DIN 47100.5Multi-core cable above core adopts core separation , white ink dot distinguish; ≥ 0,5 mm²: 5Core and below use color separation, containing yellow/Green line, matchn. DIN 47100.5Multi-core cable above the core adopts black core wire, white ink numbered to distinguish(If there are special requirements to customize)
Stranding: Stranded in layers
Outer sheath: special halogen-free compound
Jacket color: Gray RAL 7001;black RAL9005;
Rated voltage:0.5 And below 300/300V; 0.5 above 300/500V
Test voltage:0.5 above 300/500V 0.5 And below 1500V;0.5 above 2000V
Conductor resistance: In accordance with IEC 60228 cl. 5 standard
Insulation resistance: minimum 200 MΩ x km
Capacitor: core/core about 120 nF/km;
Minimum bending radius fixed:20 mm The following Ø 7,5 x d, > 20 mm The following Ø 10 x d
Minimum bending radius moved:20 mm The following Ø 15 x d, > 20 mm The following Ø 20 x d
Min. bending radius fixed:-40 °C / +90 °C ; -40 °C / +125 °C optional
Min. bending radius moved:-5 °C / +90 °C ; -5 °C / +125 °Coptional
Halogen-free:No halogen, yesIEC 60754-2standard
Smoke density:IEC 61034-2 standard
Burning behavior:Halogen-free and flame retardant, conforming IEC 60332-1-2standard
Standard:reference DIN VDE 0812
Product identification:Aein bei ke SHANGHAI AEIN WIRE & CABLE CO.,LTD Model number specification voltage CE