The cable can be laid on the upper, middle and lower floors of stucco concrete; fixedly installed indoors, outdoors or in concrete; used in buildings or industrial buildings where people or valuables are densely populated: cannot be directly buried orinstalled in water; only protected from direct sunlight. It can only be laid outdoors when it is exposed to other external influences.
· Flame retardant acc. to IEC 60332-1-2
Non-flammable performance acc. to IEC 60332-3-24
Halogen-free acc. to IEC 60754-1 (total halogen acid gas)
Combustion gas corrosivity acc. to IEC 60754-2 (acidity)
Low smoke density,
acc. to IEC 61034-2
Conductor material: bare copper wire
Conductor class: acc. to IEC 60228 cl. 5 standard
Core insulation: XLPE
Core identification: Black core with white number, with or without GNYE
Stranding: stranded in layers
Outer sheath: halogen-free, thermoplastic polyolefin mixture
Sheath color: Black,RAL 9005 Or gray RAL 7001
Rated voltage: 0.6/1kV
Testing voltage: 4 kV
Conductor resistance: acc. to IEC 60228 cl. 5 standard
Minimum bending radius fixed: 7.5 x d
Minimum bending radius moved: 15 x d
Operating temperature Fixed: -15 °C / +90 °C
Operating temperature Moved: -5 °C / +90 °C
Burning behavior: IEC 60332-1-2
Standard: HD 603-3G IEC60502
Product identification: Aein bei ke SHANGHAI AEIN WIRE & CABLE CO.,LTD Model number specification voltage CE Meter scale