The cable can be laid on the upper, middle and lower floors of stucco concrete; fixedly installed indoors, outdoors or in concrete; used in buildings or industrial buildings where people or valuables are densely populated: cannot be directly buried orinstalled in water; only protected from direct sunlight. It can only be laid outdoors when it is exposed to other external influences.
Conductor material: bare copper wire
Conductor class: acc. to IEC 60228 cl. 5standard
Insulation: XLPE
Core identification: Black core with white numbers/GNYE
Stranding: stranded in layers
Outer sheath: halogen-free, thermoplastic polyolefin mixture
Sheath color: Black, RAL 9005 Or gray RAL 7001
Rated voltage: 0.6/1kV
Testing voltage: 4kV
Conductor resistance: acc. to IEC 60228 cl. 5 standard
Minimum bending radius Fixed: 7.5 x d
Minimum bending radius Moved: 15 x d
Operating temperature Fixed: -15 °C / +90 °C
Operating temperature Moved: -5 °C / +90 °C
Burning behavior: IEC 60332-1-2
Standard: HD 603-3G IEC60502