Halogen-free installation cables with enhanced characteristics in case of fire are used for applications where harm to human life and damage to property must be prevented in the event of fire, e. g. in industrial facilities, municipal facilities, hotels, airports, underground stations, railway stations, hospitals, department stores, banks, schools, theatres, cinemas, high-rise buildings, process control centres etc. Suitable for installation in dry, damp or wet environments; for installation above, on, in and under plaster as well as in masonry walls and in concrete, however not for direct embedding in vibration, compacted or tamped concrete. Suitable for outdoor installation as long as the cable is protected against direct sunlight.
Halogen-free installation cables with enhanced characteristics in case of fire are used for applications where harm to human life and damage to property must be prevented in the event of fire, e. g. in industrial facilities, municipal facilities, hotels, airports, underground stations, railway stations, hospitals, department stores, banks, schools, theatres, cinemas, high-rise buildings, process control centres etc. Suitable for installation in dry, damp or wet environments; for installation above, on, in and under plaster as well as in masonry walls and in concrete, however not for direct embedding in vibration, compacted or tamped concrete. Suitable for outdoor installation as long as the cable is protected against direct sunlight.
Non-flammable
Low smoke and halogen-free
No corrosive and toxic gases
Ozone resistant
Conductor: Bare copper wire; single or multiple strands
Insulation color: 1 core: black or green-yellow ≤5 cores: colored >6 cores: black with continuous white numbering
Inner sheath: Filled compound total core sheath (can be omitted for single-core cables)
Outer sheath: Halogen-free polymer composite material HM2 type outer sheath complies with HM2 standard:
Sheath color: gray (RAL 7035)
Temperature range fixed: - 30 °C to +70° C
during installation: +5°C to +70° C
Permissible operating temperature of the conductor: +70°C
Short circuit temperature at the conductor: +250°C
Nominal voltage: AC U0/U 300/500 V
Test voltage core/core: 2000 V
Minimum bending radius: fixed 4x Outer-Ø
Halogen-free: complies with IEC 60754-1 standard
Flame retardant: complies with IEC 60332-3 standard
Ozone resistant: complies with IEC 60811-403 standard
Product identification :Aein beike SHANGHAI AEIN WIRE & CABLE CO,LTD Model Specification Voltage CE meter standard