For flexible use and fixed installation open-cast mining applications, in quarries, on construction sites and similar applications, with heavy mechanical stresses. The cables can be used indoors as well as outdoors, in explosion-hazard areas, in industry and in agriculture. They can be used permanently in waste water up to 40°C at a depth of max. 2000 m and in industrial water, cooling water, surface water, rainwater and mixed water - and in groundwater and seawater to a more limited extent. The requirements for accessibility and inspection depend on the consistency of the water.In aggressive water or composed of special substances, the cable's resistance properties should be tested.
For flexible use and fixed installation open-cast mining applications, in quarries, on construction sites and similar applications, with heavy mechanical stresses. The cables can be used indoors as well as outdoors, in explosion-hazard areas, in industry
and in agriculture. They can be used permanently in waste water up to 40°C at a depth of max. 2000 m and in industrial water, cooling water, surface water, rainwater and mixed water - and in groundwater and seawater to a more limited
extent. The requirements for accessibility and inspection depend on the consistency of the water.In aggressive water or composed of special substances, the cable's resistance properties should be tested.
Reaction to fire
Resistance to oil
Weather resistance Unrestricted use outdoors and indoors, resistant to ozone and moisture
Water resistance
Conductor Copper, tinned, finely stranded
Insulation material: EPR, Compound
Core identification Up to 5 cores: colored in gray, black, brown, blue, green/yellow
from 6 cores: light gray with black digits
Core arrangement Three main conductors laid-up together with the protective-earth conductor, from 50 mm² with
protective-earth conductor split into three in the outer interstices
Inner sheath Vulcanized rubber compound, Basic material: EPR, Compound
Outer sheath Vulcanized rubber compound, synthetic elastomer compound
Rated voltage 0.6/1 kV (600/1000V)
Max. permissible operating voltage AC 0.7/1.2 kV
Max. permissible operating voltage DC 0.9/1.8 kV
AC test voltage - main cores 3 kV (5 Min.)
Max. permissible temperature at conductor 90 °C
Max. short circuit temperature of the conductor 250 °C
Max. permissible water temperature 40 °C (At higher water temperatures, a shortened cable service life is to be expected)
Ambient temperature for fixed installation min -40 °C ; max +80 °C
Ambient temperature in fully flexible operation min -25 °C ; max +60 °C