For industrial and domestic installations; suitable for dry, damp and wet environments; for installation above, on, in and under plaster as well as in masonry walls and in concrete, however not for direct embedding in vibration, compacted or tamped concrete. Suitable for outdoor installation as long as the cable is protected against direct sunlight.
For industrial and domestic installations; suitable for dry, damp and wet environments; for installation above, on, in and under plaster as well as in masonry walls and in concrete, however not for direct embedding in vibration, compacted or tamped concrete. Suitable for outdoor installation as long as the cable is protected against direct sunlight.
Flame-retardant
Temperature range fixed: -40°C to +70° C during installation: +5°C to +70 ° C
Nominal voltage: AC U0/U 300/500 V
Test voltage core/core: 2000 V
Minimum bending radius fixed: 4x Outer-Ø
Conductor: bare Copper
Core insulation: PVC
1 core(s): black or green-yellow
2 - 5 core(s): colour coded
7 - 12 core(s): black cores with consecutive labeling in white digits
Cores stranded in layers with optimal lay lengths
Core sheating (filling compound) for multi-core cables
Outer sheath: PVC
Sheath colour: grey