The EN 50288-7 standard instrument cable is used for the transmission of analog and digital signals in instrument control systems, classified according to IEC79-14, and can be used in Group I Zone 1 and Zone 2 environments and cannot be directly connected to low-impedance power sources, such as public power supply stations. Recommended for indoor and outdoor installation, supports, pallets, pipelines, dry and wet environments, not recommended for direct burial. It is recommended to be used in fire prevention measures for life and important property materials.
Conductor material: bare copper wire
Conductor type :IEC 60228 Class 1 solid annealed copper conductor or Class 2 multi-strand plain copper conductor
Core wire insulation :PE
Core cable identification: black, white, and red. The cables in the three-wire group are continuously identified by numbers (1,2,,,,) on the white core.
Black/white, pairs of cables are identified consecutively with numbers (1,2,,,,) on
the white line
Pairs :2 or 3 insulated wire cores are twisted together to form pairs.
Stranding: three-wire group or pair group to lay the synthetic layer.
Subshield: Aluminum foil/polyester tape with solid tinned copper flow wire wrapped around the outer layer of the single wire group
Stranding: three wire group or pair stranding group to lay the synthetic layer.
Total shielding: Aluminum strip/polyester strip shield with 0.5mm² tinned copper drain line.
Outer sheath :LSZH composite
Jacket color: black RAL 9005 or blue
Rated voltage :300/300V
Test voltage: 1.5kV
Conductor resistance: According to IEC 60228 standard
Small bending radius fixed :7.5 x d
Small bending radius movement :15 x d
Fixed temperature rating :-30°C/+90°C
Temperature rating shift :-5°C/+90°C
Flame retardant rating: IEC 60332-1-2
Standard :BS EN 50288-7 standard
Product identification :Aein beike SHANGHAI AEIN WIRE & CABLE CO,LTD Model Specification Voltage CE meter standard