These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc...Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply. These cables are not recommended for direct burial.They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.
These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc...Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply. These cables are not recommended for direct burial.They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.
Rated voltage (U°/U): 300/500 V.
Test voltage: Urms core-core: 1000 V;
Urms core-screen : 1000 V.
Temperature range: operation : - 40° C ~ + 70° C;
installation : - 5° C ~ + 50° C.
Min. bending radius: 6 x D.
Insulation resist. (20° C): min. 25 MΩ/km.
Mutual capacitance: max. 250 pF/m (1 kHz).
Capacitance unbalanced: (1 kHz) : max. 450 pF/250 m.
Conductor: plain annealed copper wire and 0,75 mm² flexible, or 1,5 mm² stranded.
Insulation: PVC compound
Pair: two conductors twisted to a pair.
PIMF construction: polyester tape above the pair
AL-PES tape over tinned copper drain wire, 0,50 mm².
Separator: polyester tape.
Scree: AL-PES tape over tinned copper drain wire 0,50 mm².
Outer sheath: PVC compound, flame retardant
Sheath colou: black.