These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. The armour above the inner sheath protects the cable from mechanical shocks. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.
These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... Instrumentation cables are not allowed
for direct connection to a low impedance source, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. The armour above the inner sheath protects the cable from mechanical shocks. These
cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.
Rated voltage: 300 V.
Test voltage: Urms core-core: 1500 V;
Urms core-screen: 1500 V.
Temperature range: operation: - 30° C ~ + 70° C;
installation: - 5° C ~ + 50° C.
Min. bending radius: 10 x D.
Insulation resistance: min. 100 MΩ/km.
Capacitance unbalanced: (1 kHz) : max. 500 pF/500 m.
Conductor: plain copper wire, stranded.
Insulation: PVC compound, 70° C.
PIMF Construction : polyester tape above the pair, AL-PES tape over solid tinned copper drain wire, 0,60 mm.
Separator: polyester tape.
Screen: AL-PES tape over stranded tinned copper drain wire 0,50 mm².
Inner/outer sheath: PVC compound, 70° C.
Armour: galvanized round steel wire.
Sheath colour: black or blue.