These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply. These cables are not recommended for direct burial. They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.
These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... Instrumentation cables are not allowed
for direct connection to a low impedance source, e.g. public mains electricity supply. These cables are not recommended for direct burial. They are for indoor and oudoor installation, in dry and wet locations; on racks, trays,
in conduits.
Rated voltage (U°/U): 300/500 V.
Insulation resistance (20° C): min. 25 MΩ/km.
Mutual capacitance (1 kHz): max. 250 pF/m.
Capacitance unbalanced: (1 kHz) : max. 450 pF/250 m.
Test voltage: Urms core-core: 1000 V;
Urms core-screen: 1000 V.
Temperature range: operation: - 40° C ~ + 70° C;
installation : - 5° C ~ + 50° C.
Min. bending radius: 6 x D.
Conductor: plain annealed copper wire, 0,50 mm² and 0,75 mm² flexible, or 1,5 mm² stranded.
Insulation: PVC compound
Core identification: up to 40 cores; yellow with black numbers and word printed (1-40), (10,TEN); up to 80 cores; black with yellow numbers and word printed (1-40), (10,TEN).
Separator: polyester tape.
Screen: AL-PES tape over tinned copper drain wire 0,50 mm².
Outer sheath: PVC compound, flame retardant
Sheath colour:Black.