XLPE cable
  • RHW-2 90°C 600V XLPE Single Core Cable

RHW-2 90°C 600V XLPE Single Core Cable

RHW- RHW cable is an electrical wire insulated by XLPE. RHW cable can withstand heat up to 75°C and is waterproof. RHW cable is optional for use in underground and wet locations, generally suitable for lighting, power systems and general wiring applications.Can replace CUL listed RW75 model products. RHW-2-Having the same inherent qualities as RHW, NEC lists RHW-2 as being able to withstand heat up to 90°C. RHW-2 cable is suitable for direct burial in wet or dry conditions and is generally suitable for lighting,power systems and general wiring applications. Can replace CUL listed RW90 model products.

EMAILEMAIL:momo.tao@aein-cable.com

Product introduction
  • 01 Product application

    RHW- RHW cable is an electrical wire insulated by XLPE. RHW cable can withstand heat up to 75°C and is waterproof. RHW cable is optional for use in underground and wet locations, generally suitable for lighting, power systems and general wiring applications. Can replace CUL listed RW75 model products. RHW-2-Having the same inherent qualities as RHW, NEC lists RHW-2 as being able to withstand heat up to 90°C. RHW-2 cable is suitable for direct burial in wet or dry conditions and is generally suitable for lighting, power systems and general wiring applications. Can replace CUL listed RW90 model products.

  • 02 Product characteristics

    -40°C cold bending and -40°C cold impact
    Low smoke and zero halogen
    Resistant to sunlight

  • 03 Technical certification • CSA C22.2 No. 38• Conform to RoHS • We are pleased to produce special versions, other dimensions, core and jacket co- lours on request.
Product structure

Conductor material: Bare Annealed Copper

Conductor type: UL44 compliant with ASTM B3, B8 and B33 or NMX-J-008-ANCE requirements

Insulation: XLPE (Cross-Linked Polyethylene)

Core identification: optional

Rated voltage: 600V, 1000V, 2000V

Conductor resistance:UL1581 ASTM class C

Min. bending radius fixed:7.5x d

Min. bending radius moved:15x d

Operat. temp. fixed min/max:RHW:-40°C/75°C;RHW-2:-40°C/90°C

Flame retardant grade self-extinguishing and flame retardant conforms to UL1581 VW-1; CSA C22.2 No.2556-15 FT1, FT2; IEC 60332-1-2 standard

Approvals: UL

Related products