Conductor material: Bare copper or tin plating
Conductor class: acc. to UL758 standard,ASTM B3 or ASTM B33 standard,DIN VDE 0295 Conductor 5 pt.4 or. IEC 60228 Conductor 5 pt.4
Core insulation:PVC,HDPE optional
Core identification:< 20AWG:5 cores and below are distinguished by color separation, acc. to Din 47100, multi-core cables above 5 cores are distinguished by core wire color separation, and white ink is used for distinction; ≥18AWG: 5 cores and below are distinguished by color separation, including yellow/ Green ground wire, acc.to Din 47100, multi-core cables with more than 5 cores use black core wires, and white ink numbers are used to distinguish them. (customized upon request if there are special requirements
Stranding :Layered stranding
Shield:Tinned copper braid; Coverage is about70%
Outer sheath:PVC(-40 Sheath)
Sheath color: Grey RAL7001 or Black RAL9005
Rated voltage: acc. to UL: 300 V; acc. to CE:300/300 V
Test voltage:2.0 kV
Conductor resistance:UL1581 ASTM C class
Insulation resistance:PVC:+20 °C ≥ 20 MΩ x km;HDPE:+20 °C ≥ 200MΩ x km
Capacitance:core/core contract120 nF/Km; core/Masking contract160 nF/km
Minimum bending radius fixed:7.5x d
Minimum bending radius flexible:15x d
Operat. temp. fixed min/max:-15 °C / +105 °C
Operat. temp. moved min/max:-15 °C / +105 °C
Burning behavor: Self - extinguishing and flame retardant UL1581VW-1;CSA C22.2 No.2556-15 FT1,FT2;IEC 60332-1-2 standard
Approvals:UL&CUL:UL1007,UL1569,UL10450,UL2464
CE:LiYCY,Li2YCY If needed CE certification requirements should be specified separately
Product identification:Aein bei ke E503807 ® AWM Model number specification temperature voltage c® AWM Ⅰ/Ⅱ A/B specification temperature voltage FT2 SHANGHAI AEIN Meter scale SHANGHAI AEIN Model number specification voltage CE