For exposed wiring and conduits (except cable trays) in wet and dry locations. With proper handling procedures, the recommended minimum installation temperature is -40°C. Cables marked SUN RES are also suitable for outdoor use and wiring exposed to the weather.
For exposed wiring and conduits (except cable trays) in wet and dry locations. With proper handling procedures, the recommended minimum installation temperature is -40°C. Cables marked SUN RES are also suitable for outdoor use and wiring exposed to the weather.
-40° C cold bending and -40° C cold impact
Low smoke and zero halogen
Conductor material: Tinned copper or bare copper stranded wire
Conductor type: UL44 compliant with ASTM B3, B8 and B33 or NMX-J-008-ANCE requirements
Insulation: XLPE (Cross-Linked Polyethylene)
Core identification: optional
Rated voltage: 600V
Conductor resistance:UL1581 ASTM class C
Min. bending radius fixed:7.5x d
Min. bending radius moved:15x d
Operat. temp. fixed min/max:-40 °C / +90 °C
Flame retardant grade self-extinguishing and flame retardant conforms to UL1581 VW-1; CSA C22.2 No.2556-15 FT1, FT2; IEC 60332-1-2 standard
Approvals: UL