TKD CABLE
  • Alternative TKD DATEX-PIMF-CY LI2YCY-PIMF Cable

Alternative TKD DATEX-PIMF-CY LI2YCY-PIMF Cable

data transmission cable, control and connecting cable especially for cabling with high data transfer rates up to 10 Mb/s, for lossless data and signal transmission. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.

EMAILEMAIL:info@aein-cable.com

Product introduction
  • 01 Product application data transmission cable, control and connecting cable especially for cabling with high data transfer rates up to 10 Mb/s, for lossless data and signal transmission. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.
  • 02 Product characteristicsshielded single pairs by aluminium foil-clad twisted pairslargely resistant to acids, bases and specified types of oil LABS-/silicone-free (during production)suitable for maxi-termi-point applications by 7wire conductors <1 mm²
  • 03 Technical certification

    conform to RoHS conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE

     •We are pleased to produce special versions, other dimensions, core and jacket colours on request.

Product structure
Conductor material: Bare copper strand
Conductor class: 7 wired
Core insulation: PE
Core identification: Acc. to DIN 47100 different colours
Stranding: Pairs stranded in layers
Shield: Pairs in metal-foil (PiMf) with subjacent tinned drain wire
Shield3: Copper braid tinned; coverage approx. 85%
Outer sheath: PVC
Sheath colour: Grey, RAL 7032
Rated voltage: 250 V
Testing voltage: Core/core: 2 kV; core/shield: 1 kV
Conductor resistance: Loop: 0,22 mm² max. 186 Ω / km; 0,34 mm² max. 115 Ω / km; 0,50 mm² max. 78,4 Ω / km                                             
Insulation resistance: Min 5 GΩ x km
Current-carrying-capacity: Acc. to DIN VDE, s. Techn. Guidelines
Capacity: Up to 0,34 max. 70 nF/km; 0,5 mm² max. 75nF/km; 1,0 mm² max. 84nF/km (from 4 pairs)
Min. bending radius fixed: 10 x d
Min. bending radius moved: 15 x d
Operat. temp. fixed min/max: -30 °C / +80 °C
Operat. temp. moved min/max: -5 °C / +70 °C
Burning behavior: Flame-retardant acc. to IEC 60332-1-2
Standard: Similar to DIN VDE 0812