TKD CABLE
  • Alternative TKD H07V-K Cable

Alternative TKD H07V-K Cable

H05V-K and H07V-K as single core for internal wiring of devices as well as protected laying within and on shiners. Laying within pipes on-wall and in-wall permitted for signal facilities.

EMAILEMAIL:info@aein-cable.com

Product introduction
  • 01 Product application H05V-K and H07V-K as single core for internal wiring of devices as well as protected laying within and on shiners. Laying within pipes on-wall and in-wall permitted for signal facilities.
  • 02 Product characteristicslargely resistant to acids, bases and specified types of oil
    LABS-/silicone-free (during production)self-extinguishing and flame-retardant no direct laying on pallets, in channels or trays (exceptional as potential compensation)all usual standard colours available
  • 03 Technical certification

    conform to RoHS  conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
    We are pleased to produce special versions, other dimensions, core and jacket colours on request.


Product structure

Conductor material: LiYvz: copper strand tinned; H05V-K, H07V-K: bare copper strand
Conductor class: Acc. to IEC 60228 class 5
Core insulation: PVC
Core identification: Different colours
Rated voltage: H05V-K: 300/500 V; H07V-K: 450/750 V peak voltage LiYvz 500 V (0,14mm²), 900 V (0,25mm²-1,5mm²)
Testing voltage: LiYvz: 1,2 kV (0,14mm²), 2,5 kV (0,25mm²-1,5 mm²) H05V-K: 2 kV; H07V-K: 2,5 kV
Conductor resistance: At +20 °C LiYvz acc. to VDE 0812; H05V-K and H07V-K acc. to IEC 60228
Current-carrying-capacity: Acc. to. DIN VDE, see Technical Guidelines
Min. bending radius fixed: LIYvz: 10 x d // H05/07V-K: OD < 8,0 mm = 3xd; OD < 12,0 mm = 3xd; OD > 12,0 mm = 4xd - careful curve near terminal: OD < 8,0 mm = 2xd; OD < 12,0 mm = 3xd; OD >12,0 mm = 4xd
Min. bending radius moved: 15 x d
Operat. temp. fixed min/max: -30 °C / +80 °C (HAR: +70 °C)
Operat. temp. moved min/max: -5 °C / +70 °C
Burning behavior: Self-extinguishing & flame-retardant acc.to IEC 60332-1-2
Standard: LiYvz similar to VDE0812; H05/H07V-K: acc. to EN 50525-2-31 (IEC 60227-3)