halogen-free and environmentally data transmission cable, control and connecting cable predominantly for transmission of analog and digital signals in process controlled facilities in measurement and control technology, in fire vulnerable areas and facilities with high concentration of people and property values, for lossless transmission of datas and signals. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.
•conform to RoHS •conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
•We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: | Bare copper strand |
---|---|
Conductor class: | Acc. to IEC 60228 cl. 5; exception: 0,34 mm², stranded (7 x 0,25 mm) |
Core insulation: | Special halogen-free compound |
Core identification: | Acc. to DIN 47100 different colours |
Stranding: | Stranded in layers |
Shield3: | Copper braid tinned, coverage approx. 85% |
Outer sheath: | Special halogen-free compound |
Sheath colour: | Grey, RAL 7001 |
Rated voltage: | Uo/U: 250 V; peak-voltage on 0,14 mm² 350 V; > 0,14 mm² 500 V |
Testing voltage: | On 0,14 mm²: core/core 1,2 kV; core/shield 1 kV > 0,14 mm²: core/core 1,5 kV; core/shield 1 kV |
Conductor resistance: | Nach IEC 60228 cl. 5 |
Insulation resistance: | Min. 20 MΩ xkm |
Current-carrying-capacity: | Acc. to DIN VDE, s. Techn. Guidelines |
Capacity: | Core/core ca. 120 nF/km; core/shield ca. 160 nF/km |
Min. bending radius fixed: | Up to 20 mm Ø 7,5 x d, > 20 mm Ø: 10 x d |
Min. bending radius moved: | Up to 20 mm Ø 15 x d, > 20 mm Ø 20 x d |
Operat. temp. fixed min/max: | -30 °C / +80 °C |
Operat. temp. moved min/max: | -5 °C / +70 °C |
Halogen free: | Acc. to IEC 60754-2 |
Burning behavior: | Flame-retardant acc. to IEC 60332-3-24 (Cat. C) |
Standard: | Similar to DIN VDE 0812 |