power, control and connecting cable for drive systems with frequency converter technology, for fixed laying and casually movement without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use, but no laying underground.
•conform to RoHS •conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
•We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: | Bare copper strand |
---|---|
Conductor class: | Acc. to IEC 60228 cl. 5 |
Core insulation: | XLPE |
Core identification: | Acc. to DIN VDE 0293-308 coloured cores with GNYE |
Stranding: | Stranded in layers |
Shield3: | Alu-lamin. polyester foil, metal side outside, cover. 100% under copper braid tinned |
Outer sheath: | PVC |
Sheath colour: | Transparent; K-version: black |
Rated voltage: | Uo/U 0,6/1 kV - highest permissible operating voltage Single phase and three-phase: 700/1200 V, DC operation: 900/1800 V |
Testing voltage: | 4 kV |
Conductor resistance: | Acc. to IEC 60228 cl. 5 |
Insulation resistance: | Min. 200 MΩ x km |
Current-carrying-capacity: | Look at the table on the right side |
Capacity: | Look at the table on the right side |
Min. bending radius fixed: | ≤ 12mm Ø: 5 x d; ≤ 20mm Ø: 7,5 x d; > 20mm Ø: 10 x d |
Min. bending radius moved: | ≤ 12mm Ø: 10 x d; ≤ 20mm Ø: 15 x d; > 20mm Ø: 20 x d |
Operat. temp. fixed min/max: | -40 °C / +90 °C |
Operat. temp. moved min/max: | -5 °C / +90°C, K-version: -15 °C / +90°C |
Temp. at conductor: | + 90 °C in operation; +250 °C in case of short-circuit |
Burning behavior: | Self-extinguishing & flame-retardant acc.to IEC 60332-1 |