The cable can be laid on the upper, middle and lower layers of stucco concrete; Used in buildings or industrial buildings where people or valuables are dense; Cannot be directly buried or installed in water; Suitable for outdoor use, but pay attention to the temperature range and must be protected from direct sunlight.
Used in buildings or industrial buildings where people or valuables are dense; For the connection of critical equipment such as elevators, fire systems, lighting systems, etc.; In public facilities such as hospitals, schools, shopping malls, etc., all internal wiring.
03· Flame retardant in line with CPR B2ca-s1a,d0,a1 class
· Non-delay performance in accordance with IEC 60332-3-24
· Halogen-free according to IEC 60754-1(total halogen acid gas)
· Combustion gas corrosivity in accordance with IEC 60754-2(acidity)
· Low smoke density in accordance with IEC 61034-2
· Comply with RoHS standards
·Comply with CPR certification standards
·Comply with Directive 2014/35/EU-Guideline (" Low Voltage Directive ")CE
Conductor material: bare copper or tinned copper
Conductor grade: According to IEC 60228 cl.5 standard
Insulation :XLPE
Core identifier: Black core with white number (customizable color)
Stranding: stranding in layers
Outer sheath :LSZH
Jacket color: Black RAL9005 (customizable color)
Rated voltage :0.6/1 kV
Test voltage :4 kV
Conductor resistance: According to IEC 60228 cl.5 standard
Bending radius: 7.5 x d for mobile installation 15 x d for simultaneous installation
Temperature range :-40°C/+90°C
Flame retardant class :CPR B2ca-s1a,d0,a1
Product identification :Aein beike SHANGHAI AEIN WIRE & CABLE CO.LTD Model Specification Voltage CE meter standard