These power cables with special performance for use in power stations and intended supply power to equipments which must operate in fire conditions and during fire fighting. Suitable for indoor applications, outdoor applications, protection must be provided against exposure to direct sunlight. If th cable laid directly in earth a protective conduit should have to be used.
fire resistant, flame retardant, halogen-free
•C onform to 2014/35/EU-Guideline (''Low voltage Directive'') CE •We are pleased to produce special versions, other dimensions, core and jacket co- lours on request.
CONDUCTOR: Electrolytic annealed, class 1 solid (RE) or class 2 (RM) stranded plain
copper wires
INSULATION: Special fire resistant cross linked compound, type HIC
CORE IDENTIFICATION: According to DIN VDE 0293-308, HD 308 S2 or EN 50334
INNER COVERING: Special flame retardant, halogen-free compound
SHEATH: Halogen-free flame retardent compound, type HMT1
COLOR: Orange
RATED VOLTAGE: 600 / 1000 V
AC TEST VOLTAGE: 4 kV
OPERATING TEMPETATURE: -30°C to +90°C
CONDUCTOR SHORT-CIRCUIT TEMP.: 250°C (Max. 5 sec.)
MIN. INSTALLATION TEMP.: -5°C
MIN. BENDING RADIUS
(during installation)
Single Core Cable: 15 x Outer Diameter
Multi Core Cable: 12 x Outer Diameter
MAXIMUM PERMISSIBLE TENSILE STRESS: with cable grip for Cu: 50 N/mm2