Internal appliance wiring, electronic circuits, switchboards, fluorescent ballasts, instrument panels, recreational vehicles Motor and transformer leads, hookup wire, and marine cable.TW: Designates a single conductor with flame retardant, moisture resistant thermoplastic insulation. Wire rating is 60℃ wet or dry.THW: Designates a single conductor with moisture resistant, heat resistant thermoplastic insulation. Wire rating is 75℃ wet or dry.THW-2: Same as THW, but wire rating is 90℃ wet or dry. THHW: Indicates a single conductor with flame retardant, moisture and heat resistant thermoplastic insulation. The conductor is rated for 90°C dry and 75°C wet.
Excellent sunlight, gas, heat, humidity, oil, water and acid resistance03
Conductor material: bare copper, tinned copper optional
Conductor type: UL83 compliant, ASTM B3, B8 and B33 or NMX-J-008-ANCE compliant
Core insulation: PVC
Core identification: optional
Product model interpretation: T = Thermoplastic
HH = High heat resistance
N = Nylon coating
H = Heat resistant
W = Waterproof
Rated voltage: 600V
Test voltage: 14AWG-2AWG: 2.0KV; 1AWG-4/0AWG: 2.5kV; 250kcmil-500kcmil: 3.0kV; 550kcmil-1000kcmil: 3.5kV; 1100kcmil-12000kcmil: 4.0kV
Conductor resistance: UL1581 ASTM Class C
Min. bending radius fixed:7.5x d
Min. bending radius moved:15x d
Minimum/maximum fixed operating temperature: THW-2: -40°C/90°C; THW: -40°C/75°C; TW: -40°C/60°C; THHW: -40°C/90°CFlame retardant grade: self-extinguishing and flame retardant in accordance with UL1581 VW-1; CSA C22.2 No.2556-15 FT1, FT2; IEC 60332-1-2 standards
Approval: UL